HK-K06 - January 13th, 2009
Notes
- Warm heater. Surface temperatures are being tracked for damper comparisons, and data will be added later.
- Damper closed at end of run. (Jan 17/09: damper was found not to be closing all the way. See notes in Testing Series.)
- White birch, 20% moisture
- 6 pieces, 4.5 lb kindling, 63.2 lbs total
- First test with grate air open. Note the higher stack temperatures compared to the previous 5 K-series runs.
- Noticeably better burn. Low CO, low PM
- 0.59 g/kg PM (Condar)
- 11.43 g/kg CO
- 72.1 % overall efficiency
- NOTE: Condar spreadsheet calculation was modified, starting with this run. The old spreadsheet was set up for gas readings at 5 minute intervals, which were entered from the TESTO data spreadsheet. Now, the averages are calculated directly off the TESTO data, at 30 second intervals, instead of 5 minutes.
- False start, had to light kindling newspaper at middle of pile.
Animation
Flue Gas
Opacity
Malfunction. Sensor got sooted up, and was cleaned at the 38 minute mark.
Statistics
Fuel stack
Resources
- Excel Data File: Unavailable
- Condar Spreadsheet + Fueling Excel Data File: Unavailable