HK-K06 - January 13th, 2009

Notes
  • Warm heater. Surface temperatures are being tracked for damper comparisons, and data will be added later.
  • Damper closed at end of run. (Jan 17/09: damper was found not to be closing all the way. See notes in Testing Series.)
  • White birch, 20% moisture
  • 6 pieces, 4.5 lb kindling, 63.2 lbs total
  • First test with grate air open. Note the higher stack temperatures compared to the previous 5 K-series runs.
  • Noticeably better burn. Low CO, low PM
  • 0.59 g/kg PM (Condar)
  • 11.43 g/kg CO
  • 72.1 % overall efficiency
  • NOTE: Condar spreadsheet calculation was modified, starting with this run. The old spreadsheet was set up for gas readings at 5 minute intervals, which were entered from the TESTO data spreadsheet. Now, the averages are calculated directly off the TESTO data, at 30 second intervals, instead of 5 minutes.
  • False start, had to light kindling newspaper at middle of pile.
Animation

Anim-K06.gif

Flue Gas

gas-HK-K06.gif

Opacity

opacity-HK-K06.gif

Malfunction. Sensor got sooted up, and was cleaned at the 38 minute mark.

Statistics

Condar-HK-K06.gif

Fuel stack

K06-02.jpg

K06-00.jpg

Resources
  • Excel Data File: Unavailable
  • Condar Spreadsheet + Fueling Excel Data File: Unavailable